BASIC FEATURES:
- » Multi-input and multi-range performance
» Large 20mm bright display (SR3)
» Dust and splash proof front panel NEMA4X / IP66 - DOWLOAD CATALOGE SHIMADEN
-
ORDERING INFORMATION:
ITEM CODE SPECIFICATIONS SERIES SR1- MPU-Based Auto-Tuning PID Digital Controller, DIN H48 x W48 x D111mm SR3- MPU-Based Auto-Tuning PID Digital Controller, DIN H96 x W96 x D111mm SR4- MPU-Based Auto-Tuning PID Digital Controller, DIN H96 x W48 x D111mm INPUT 8 (Multi input) Thermocouple: B, R, S, K, E, J, T, N, PLII, WRe5-26 {U, L (DIN 43710)} R.T.D.: Pt100 Ω / JPt100 Ω
Voltage(mV): -10~10, 0~10, 0~20, 0~50, 10~50, 0~100mV DC
6 Voltage (V): -1~1, 0~1, 0~2, 0~5, 1~5, 0~10V DC Current (mA): 0~20mA DC:(V) 0~5V DC, 4~20mA DC:(V) 1~5V DC (applied via enclosed 250Ω shunt resistor)
CONTROL OUTPUT Y- Contact 1a Contact capacity: 240V AC 2.0A/resistive load Proportional cycle: 1~120 seconds I- Current 4~20mA DC Load Resistance: 600Ω max. P- SSR drive voltage 12V ±1.5V DC 30mA max. Proportional cycle:1~120 seconds V- Voltage 0~10V DC Load current: 2mA max. EVENT OUTPUT 1 Event output (1a) x 2 points, Contact capacity: 240V AC 1A/resistive load REMARKS W Without X With (Please consult before ordering.) MEASURING RANGE CODES:
Type of input Code Scaling range Thermocouple B *1 01 0 ˜ 1800 °C 0 ˜ 3300 °F R 02 0 ˜ 1700 °C 0 ˜ 3100 °F S 03 0 ˜ 1700 °C 0 ˜ 3100 °F K *3 04 -199.9 ˜ 400.0 °C -300 ˜ 750 °F 05 0.0 ˜ 800.0 °C 0 ˜ 1500 °F 06 0 ˜ 1200 °C 0 ˜ 2200 °F E 07 0 ˜ 700 °C 0 ˜ 1300 °F J 08 0 ˜ 600 °C 0 ˜ 1100 °F T *3 09 -199.9 ˜ 200.0 °C -300 ˜ 400 °F N 10 0 ˜ 1300 °C 0 ˜ 2300 °F PLII *4 11 0 ˜ 1300 °C 0 ˜ 2300 °F WRe5-26*5 12 0 ˜ 2300 °C 0 ˜ 4200 °F U *2, *3 13 -199.9 ˜ 200.0 °C -300 ˜ 400 °F L *2 14 0 ˜ 600 °C 0 ˜ 1100 °F R.T.D. Pt100 31 -200 ˜ 600 °C -300 ˜ 1100 °F 32 -100.0 ˜ 100.0 °C -150.0 ˜ 200.0 °F 33 -50.0 ˜ 50.0 °C -50.0 ˜ 120.0 °F 34 0.0 ˜ 200.0 °C 0.0 ˜ 400.0 °F JPt100 35 -200 ˜ 500 °C -300 ˜ 1000 °F 36 -100.0 ˜ 100.0 °C -150.0 ˜ 200.0 °F 37 -50.0 ˜ 50.0 °C -50.0 ˜ 120.0 °F 38 0.0 ˜ 200.0 °C 0.0 ˜ 400.0 °F Voltage (mV) -10 ˜ 10 71 Optional setting of Measuring range is
possible by the scaling function as
shown below.Scaling range: 1999~9999 count
Span: 10~5000 count
Lower limit value < Upper limit value
Position of decimal point
: None
: Decimal point below digits, 1, 2, 30 ˜ 10 72 0 ˜ 20 73 0 ˜ 50 74 10 ˜ 50 75 0 ˜ 100 76 Voltage (V) -1 ˜ 1 81 0 ˜ 1 82 0 ˜ 2 83 0 ˜ 5 84 1 ˜ 5 85 0 ˜ 10 86 Note:
*1 Thermocouple B: Accuracy guarantee not applicable Temp. below 400 C.
*2 Thermocouple U, L: DIN 43710
*3 Thermocouple K, T, U: Accuracy guarantee not applicable Temp.
below –100.0 C (1.0%FS+1digit) & –100.0 0.0 C (0.5%FS+1digit)
*4 Thermocouple PLII: Platinel
*5 Thermocouple WRe5-26: ASTM988
*Unless otherwise specified, following setting will be applied for shipment.Input Specification / Rating Measuring range Multi input K thermocouple 0.0 ˜ 800.0 °C Voltage (V) 0 ˜ 10V DC 0.0 ˜ 100.0 Control Output Control Mode Y ON-OFF (P=OFF) I, P, V PID Control (P=3.0) SPECIFICATIONS:
Model SR1 : 48 x 48 Digital Controller SR3 : 96 x 96 Digital Controller SR4 : 96 x 48 Digital Controller Display Digital display: SR1, SR4 (PV)/4 digit 7 segments red LED (H: 11mm)
(SV)/4 digit 7 segments green LED (H: 9.5mm)SR3 (PV)/4 digit 7 segments red LED (H: 20mm)
(SV)/4 digit 7 segments green LED (H: 13mm)Display accuracy: ± (0.3%FS + 1 digit) (see “Note” in Measuring Range Codes)
(Excluding cold junction compensation accuracy)Display accuracy maintaining range: 23°C ± 5°C Display resolution: Depends on measuring range (0.001, 0.01, 0.1, 1) Display updating cycle: 0.5 seconds Action display: 5 LED lamp displays (OUT/EV1/EV2/AT/MAN) Input Type of input: Selectable from multiple (TC,Pt,mV) and voltage (V)
*Current input 0-20mA DC (Voltage: 0-5V), 4-20mA DC
(Voltage: 1-5V) applied via 250Ω shunt resistorThermocouple: B,R,S,K,E,J,T,N,PL II,WRe5-26, {U,L(DIN 43710)} Input impedance: 500kΩ minimum External resistance tolerance: 100 Ω maximum Burnout function: Standard feature (up scale) Cold junction compensation accuracy: ± 1°C (within 23°C ± 5°C)
± 2°C (ambient temperature: 5°C to 45°C)R.T.D.: Pt100/JPt100, 3-wire type Amperage: 0.25 mA Lead wire tolerance: Lead wire tolerance:5 Ω max/wire
(3 lead wires should have the same resistance.)Voltage mV: -10~10,0~10,0~20,0~50,10~50, 0~100mv DC (Burnout) Up scale at time of abnormal input V: -1~1, 0~1, 0~2, 0~5,1~5, 0~10V DC Input impedance: 500kΩ minimum Input scaling function: Scaling possible for voltage (mV,V) or current (mA) input Scaling range: -1999~9999 counts Span: 10~5000 counts Decimal point: (Position) None, 0.0, 0.00, 0.000 Sampling cycle: 0.5 seconds PV bias: -1999~2000 units PV filter: 0~100 seconds solation: Insulated between input and output (not insulated between input and system) Control Control mode: Expert PID control with auto tuning function Proportional band (P): OFF, 0.1~999.9%(ON-OFF action by OFF) Integral time (I): OFF, 1~6000 seconds (P or PD action by OFF) Derivative time (D): OFF, 1~3600 seconds (P or PI action by OFF) Manual reset: -50.0~50.0% (Effective when I=OFF) ON-OFF hysteresis: 1~999 units (Effective when P=OFF) Proportional cycle: 1~120 seconds (for contact and SSR drive voltage output) Control output characteristic: RA (reverse action characteristic)/DA (direct action
characteristic) is selectable (Default setting =RA)
*P=OFF by default for contact output, others: PID controlType of control/rating: Contact: 1a 240V AC 2A (resistive load) SSR drive voltage: 12V ±1.5V DC (Max load current 30mA) Voltage: 0~10V DC (Max load current 2mA) Current: 4~20mA DC (Max load resistance 600 Ω ) Control output resolution: Approx.0.5%(1/200) Isolation: Output isolated from all Event output Number of events: Total 2 points of EV1 and EV2 as standard Type: Selectable from the following 8 types for EV1 and EV2:
No selection, Higher limit deviation, Lower limit deviation,
Outside higher/lower limit deviations, Within
higher/lower limit deviations, Higher limit absolute value,
Lower limit absolute value, ScaleoverEvent setting range: Absolute values: (both higher limit and lower limit): Within
measuring range, Deviations: (both higher limit and
lower limit): -1999~2000 units, Higher/lower limit
deviations (within/outside): 0~2000 unitsEvent action: ON-OFF action Hysteresis: 1~999 units Standby action: Selectable from the following 4 types (EV1 and EV2) (1) None. (2) Standby when power is applied. (3) Standby
when power is applied and when SV value in execution
is changed. (4) Control mode without standby action
(No alarm is output at the time of abnormal input).Output type/rating: Contact (1a x 2 points common)/240V AC 1A (resistive load) Output updating cycle: 0.5 seconds Action display: 2 LED lamp displays (EV1/EV2) General Specifications Data storage: Non-volatile memory (EEPROM) Operating conditions: (Ambient temperature) -10~50 °C
(Ambient humidity) 90%RH or less (no dew condensation)
(Altitude) 2000m from the sea level or lower
(Category) II, (Degree of pollution) 2Storage temperature: -20~65°C Supply voltage: 100-240V AC±10% 50/60Hz Power consumption: 10VA 240V AC, 6VA 100V AC Input/noise (Normal mode) 40 dB or higher (50/60 Hz) removal ratio: (Common mode)120 dB or higher (50/60 Hz)
For Voltage (V) input: 90 dB or higher (50/60 Hz)Applicable standards: Safety: IEC61010 and EN61010-1
EMC: EN61326 (Class A: Industrial environment)Insulation resistance: Input/output – power supply: 500V DC 20MΩ or above
Input/output – contact output: 500V DC 20MΩ or aboveDielectric strength: Input/output – power supply: 2300V AC 1 minute
Contact output – power supply: 2300V AC 1 minuteProtective structure: Only front panel has dust-proof and drip-proof structure
NEMA4X and IP66Material / Color of case: PPO resin molding (equivalent to UL94V-1) / Ivory External dimensions: SR1: H48 x W48 x D111 (Panel depth: 100) mm
SR3: H96 x W96 x D111 (Panel depth: 100) mm
SR4: H96 x W48 x D111 (Panel depth: 100) mmMounting: Push-in panel (one-touch mount) Panel thickness: 1.0~4.0 mm Panel cutout / Weight: SR1: H45 x W45 mm / Approx. 150 g
SR3: H92 x W92 mm / Approx. 270 g
SR4: H92 x W45 mm / Approx. 190 g